Specification
1.5-3.0 kVA
Maintenence Bypass Switch
Single Input
Rack Mount / Wall Mounting Format
115 VAC & 230 VAC Versions
XT MBS Series
Input
Input Voltage 115 V single phase, 80-138 V
230 V single phase, 176-276 V
Output
Output Voltage 115 V single phase, 80-138 V
230 V single phase, 176-276 V
Output Regulation See Output Characteristics Table
General
Dimensions See Output Characteristics Table
IP Rating IP30
Connector Type Contact Sales Team
1
Environmental
Operating Temperature 0 ˚C to +40 ˚C
Storage Temperature -10 ˚C to +85 ˚C
Operating Humidity <0-95% RH, non-condensing
Storage Humidity <0-95% RH, non-condensing
Operating Altitude 1000 metres
Shock & Vibration <2 g
EMC & Safety
Safety Standards EN60947 1999 low voltage switchgear
& control gear
Product Description
The Maintenance Bypass Switch (MBS) permits the maintenance or repair of a UPS system by providing a simple but efficient means of
temporarily isolating/removing the UPS from the power circuit without interrupting power to the critical load.
Output Characteristics
Single Phase/Single Feed Input
Rating Voltage Current Format Dimensions (H ,W, D) Model Number
1.5 kVA 230 V 10 A 19” Rack 1U x 19” x155mm XT BBSR 1k6
3.0 kVA 230 V 16 A 19” Rack 1U x 19” x155mm XT BBSR 3k2
1.5 kVA 230 V 10 A Wall 235 x 215 x80mm XT BBSW 1k6
3.0 kVA 230 V 16 A Wall 235 x 215 x80mm XT BBSW 3k2
1.5 kVA 115 V 16 A 19” Rack 1U x 19” x155mm XT BBSR 1k6 115V
3.0 kVA 115 V 32 A 19” Rack TBA TBA
1.5 kVA 115 V 16 A Wall 445 x 400 x100mm XT BBSW 1k6 115V
3.0 kVA 115 V 32 A Wall TBA TBA
Single Input Bypass
Xi BB
Xi UPS
UPS I/P 1
UPS O/P
Mains Feed 1
Output to Load
Single Phase / Single Feed Input
UPS/INVERTERS