Uninterruptible Power Supplies
Input Voltage (full load 115VAC version: 80-138VAC / 230VAC version: 176-276VAC
without using batteries)
Input Frequency 46-64Hz
Input Power Factor >0.98 at full load
Input Protection Fuse/Breaker
Output Voltage 115VAC nominal - 100/110/115/120VAC selectable
230VAC nominal - 208/220/230/240VAC selectable
Output Regulation ±2% of nominal
Output Waveform Sine Wave
Output THD <3% linear load
Crest Factor 3:1
Output Protection Electronic Overload Protection (ultimately by fuse/breaker)
Efficiency (AC-AC) 86% typical
Overload Capacity See Overload Characteristics
Output Frequency 50/60Hz dependant on input
Internal Battery Type VRLA 5 year design life. For 10 year option add suffix ‘X’ to model number
Recharge <4 hours to 90%, single battery set, <16 hours to 90%, 4 battery sets
Battery String Voltage 48VDC
Autonomy See Tables
Temperature Autonomy, recharge & battery life based on 25°C ambient
Input Receptacles IEC
Output Receptacles IEC
Display/Alarm Front panel LED menu driven, audible alarms. See front panel layout
Interface (Rear Panel) 1 x RS232 & 1 x USB (fitted in option slot)
Software Supplied bundled to support Windows 95, 98, ME, 2000, XP & NT
Fitted Fuse/Breaker WM1500 - 10A, WM1500L CE - 15A
REPO Remote emergency power off, must be fitted for unit to function. Connector on base of unit. Remove
link to shut down output in AC mode or shut down unit in battery mode
Operating Temperature -10°C to +40°C
Storage Temperature -15°C to +50°C
Operating Humidity 0-95% RH non-condensing
Operating Altitude 3000m without derating
Acoustic Noise <45dBA at 1 metre
Ingress IP43 standard, option for IP45
Emissions EN55022 level B, EN50091-2 level B
ESD Immunity EN61000-4-2, level 3
Radiated Immunity EN61000-4-3, level 2
EFT/Burst EN61000-4-4, level 2
Surge EN61000-4-5, level 3
Safety Standards EN50091-1-1, EN60240-1-1, EN60950, CE
Electrical Specification
WM Series
1500VA
True On-Line
Features
Wallmount Format
Optional 10 year batteries
Backlit LCD
www.powersolve.co.uk
Above: Closed cabinet with key locks.
Right: WM1500 series
Consists of UPS Electronic
module mounted in wall cabinet
with up to 4 battery sets.
UPS Electronic module available
as separate item.
Page view 0
1 2 3 4 5

Summary of Contents

Page 1 - True On-Line

Powersolve Electronics Ltd. 8A Arnhem Road, Newbury, RG14 5RU. EnglandTel: 01635 521858 Fax: 01635 523771 Email: [email protected]

Page 2 - WM1500-x

Powersolve Electronics Ltd. 8A Arnhem Road, Newbury, RG14 5RU. EnglandTel: 01635 521858 Fax: 01635 523771 Email: [email protected]

Page 3

Powersolve Electronics Ltd. 8A Arnhem Road, Newbury, RG14 5RU. EnglandTel: 01635 521858 Fax: 01635 523771 Email: [email protected]

Page 4 - Software Options

Powersolve Electronics Ltd. 8A Arnhem Road, Newbury, RG14 5RU. EnglandTel: 01635 521858 Fax: 01635 523771 Email: [email protected]

Page 5 - TIME (seconds)

Powersolve Electronics Ltd. 8A Arnhem Road, Newbury, RG14 5RU. EnglandTel: 01635 521858 Fax: 01635 523771 Email: [email protected]

Comments to this Manuals

No comments