Powersolve 600S Seires User Manual

Browse online or download User Manual for Power suppliers Powersolve 600S Seires. Powersolve 600S Seires User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 2
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
U
nit 8A
Arnhem Road
Newbury. RG14 5RU
Te
l: +44 (0) 1635 521858
Fax: +44 (0) 1635 523771
www.powersolve.co.uk
600 S - Se ries 600 W SWITCHED MODE DC POWER SUP PLY
Fea tures :
Very high re li abil ity, MTBF 1.000.000 hrs No RFI prob lems, RFI fil ters in out put and in put
Natural convection cooling Meets EN 61000-3-2 and V DE 0160 class 2
Thermally over-rated for high ambient temperature without derating Low inrush current
Build-in diode for redundant parallel operating High efficiency 89%
Under-voltage alarm contact Short circuit protected
Low output ripple, 7 mV rms Analog programmable
Spec i fi ca tions :
Input voltage : AC 198-264 V 48-62 Hz 3.8 Arms Line distortion : Harmonic current meets EN 61000-3-2
fuse 6.3 A T, crest factor 2.0 Safety : EN 60950, EN 61010 SELV / PELV
: AC 99-132 V 48-62 Hz 7.6 Arms Output voltage : Screwdriver adjustable with 10-turn
fuse 12.5 A T potmeter at the rear side.
: DC contact factory Factory set at 24.0 V
Insulation Also analog programable by 2-5 V
Input / output : 3750 V rms (1min) Efficiency : 89% at 230 V AC input and 600 W output
Input / case : 2500 V rms (1min) (max. heat dissipation 74 W)
Output / case : 500 V DC Temp. coeff : 5.10-5 per °C
Stability : 3.10-4 during, 8 hrs under constant
conditions, after 1 hr warmup.
Inrush current : Limited by 47 Ohm (shorted after startup) Regulation
Load 0 - 100% : Better than 10 mV
Power factor : 0.76 at 230 V AC input and full load. line 198-264 V : Better than 5 mV
Ripple + noise : Max 7 mV rms, 20 mV pp (BW = 20 MHz)
EMC : EN 61204-3 Power Supply Standard Output imp. : Less than 0.05 Ohm up to 100 kHz
: EN 61000-6-3 Emission (EN 55022B) Recovery time : 0.3 milliseconds to recover to within
: EN 61000-6-2 Immunity 100 mV after a 50 to 100% load step
Max. deviation 300 mV
VDE0160 impulse test : Input with stands non periodic impulse Hold-up time : 30 ms at 155 or 230 V AC input and full
2.3 Ûn 1.3 ms of VDE0160 class 2 load. 60 ms at half load.
Series operations : up to 500 V total voltage
Parallel oper. : No restrictions
Redundant parallel : Use R+ connection via build-in Schottky
operation diode to separate the outputs. Do not use
remote sensing.
600 S 24 12 -15 V 30 A
24 V 25 A
30 V 20 A
Mod els Volt age range Cur rent range
600 S 24 12 -15 V 30 A
24 V 25 A
30 V 20 A
Page view 0
1 2

Summary of Contents

Page 1

Unit 8AArnhem RoadNewbury. RG14 5RUTel: +44 (0) 1635 521858Fax: +44 (0) 1635 523771www.powersolve.co.uk 600 S - Se ries 600 W SWITCHED MODE DC

Page 2

600S24Page 2 SPECIFICATIONS Rev. Sept. 2012• Under voltage alarm contact : Changes over when output voltage drops • Overload Protection: Continuous o

Comments to this Manuals